Heimeier single-pipe Heimeier base 3871-02.000 gunmetal nickel-plated, with blue protection cap
Available for order
delivery time: 10-28 working days
Shipping Cost Points: 50
Part Number: 387102000
Questions about the article?
+49 241-51832611
Mon. - Thu. 8.00 am to 6.00 pm, Fri. 8.00 am to 3.00 pm
Details
Heimeier single pipe Heimeier lower part 3871-02.000
- One-pipe valve made of gunmetal nickel-plated with immersion pipe for Radiators with one-point Radiators on the side
- the center distance of the pipe connections is 58 mm
- the fitting consists of a single-pipe valve base
- Immersion tube (short or long version) and baffle plate
- Pipe side connection G 3/4
- with compression fitting for plastic
- Copper-
- Precision steel or composite pipe
- for the single-pipe valve lower part only the associated ones
- use marked compression fittings (marking e.g. 15 THE)
- The Spezial regulating Spezial ensures an almost constant mass flow in the ring main
- In the design case, the radiator share is 35% of the ring mass flow
- Flow and return can be shut off
- whereby the Radiators during operation without emptying the system
- the bypass remains open regardless of the shut-off
- so that the circulation of the ring main is not interrupted
- the immersion tubes are available in 2 different lengths depending on the application
- the long immersion tube (screw-in length 250 mm) is necessary when installing DIN
- Tubular and narrow tube radiators with more than 10 sections should be used
- otherwise the short immersion tube (screw-in length 85 mm)
- the 2000 in the middle of the 2000 for both immersion tubes. Link installed
- When using plate and special radiators, a two-chamber connection with a Ø 11 mm hole must be available or the radiator connection must be attached in this way
- that the long immersion tube can be inserted without a baffle plate
- Distributor inserts and separating elements as well as the immersion tube length are to be installed according to the installation instructions of the respective radiator manufacturer
- Problem-free dismantling of the heater by separating the immersion tube in the screw connection
- the direction of flow marked on the single-pipe valve must be observed
- since the Radiators not properly flowed through if the connection is Radiators
Downloads (1)
** Average Wholesale Price