Jung Basiclogo control JP44439 AD 46 EXM,TLS, 15 m, with dynamic pressure level sensor
Available for order
delivery time: 10-28 working days
Shipping Cost Points: 250
Part Number: JP44439
Questions about the article?
+49 241-51832611
Mon. - Thu. 8.00 am to 6.00 pm, Fri. 8.00 am to 3.00 pm
Details
Jung Basiclogo control JP44439
- Control for level-dependent switching on and time-dependent switching off of a direct starting
- explosion-proof three-phase submersible pump
- preferably MultiCut pump
- Two independent dynamic pressure level sensors for 'On/Off' and automatic emergency switching with alarm message as standard
- ATEX-compliant monitoring of motor temperature and running time
- Dry-run protection with immersion switch and safety barrier
- Adjustable pump run-on time (1-60s)
- with coupled switch-on delay
- (0-10s) after power failure
- Indicator lights for pump operation
- Motor overcurrent
- Engine overtemperature
- Engine running time exceeded
- Flood
- Water shortage
- Rotating field wrong
- Alarm system (network dependent): potential-free and acknowledgeable closer
- e.g. for connecting a 230 V flashing or warning light
- optionally cyclic potential-free contact for remote fault reporting electronic buzzer
- optionally clocked and acknowledgeable Battery charging circuit for mains-independent operation of the alarm system using an optional battery
Downloads (5)
** Average Wholesale Price